Clean Environment
OLYMPIA KOGYO CO.,LTD.
Standard specifications
Air
High Temp.Air
Please consult about special specifications other than above-mentioned
standard ones.
The specifications and the dimensions might be changed without an advanced
notice for the improvement.
1. Duct Burner ass'y 2. Burner head 3.
Fan casing 4. Air inlet 5. Fan motor 6.
First cutoff valve
7. Second cutoff valve 8. Pilot solenoid valve 9.
Pilot governor 10. Gas pressure switch 11.
Air pressure switch 12. Pilot cock 13.
Main cock 14. Ignition transformer 15. Module control motor 16. Flame
rod 17. Ignition bar 18. Relay terminal
box 19. Inspection door 20.Sight window 21. Combination
flange
22. Base frame 23. Butterfly valve
Type |
CD-50PW |
CD-100PW |
CD-200PW |
CD-300PW |
CD-400PW |
CD-500PW |
The maximum input (kW) |
58 |
116 |
233 |
350 |
465 |
580 |
Fuel consumption |
LP gas |
2.1 |
4.2 |
8.3 |
12.5 |
16.7 |
20.8 |
13A gas |
4.6 |
9.1 |
18.2 |
27.3 |
36.4 |
45.5 |
6B gas |
10 |
20 |
40 |
60 |
80 |
100 |
6C gas |
11.1 |
22.2 |
44.4 |
66.7 |
88.9 |
111.1 |
Supply pressure
(mmH20) |
LP gas |
280 |
13A gas |
200 |
6B・6C gas |
100 |
Power source |
200V 3φ |
Capacity of motor(kW) |
0.25 |
0.25 |
0.4 |
0.75 |
0.75 |
1.5 |
Combustion method |
Pre-Mixing |
Duct cross section (mm) |
500×320 |
700×500 |
950×700 |
1100×900 |
1300×1000 |
1500×1100 |
Connecting pipe diameter(B) |
LP gas |
1/2 |
3/4 |
1 |
1-/1/4 |
13A gas |
1/2 |
3/4 |
1 |
1-/1/4 |
1-/1/2 |
6B・6C gas |
3/4 |
1 |
1-/1/2 |
2 |
2-/1/2 |
3 |
Turn down ratio |
1:3 |
1:5 |
1:10 |
Type |
The maximum input(kW) |
A |
B |
C |
D |
E |
CD−50PW |
58 |
1150 |
1020 |
875 |
650 |
130 |
CD−100PW |
116 |
1150 |
1200 |
1055 |
850 |
130 |
CD−200PW |
233 |
1150 |
1440 |
1275 |
1100 |
130 |
CD−300PW |
350 |
1350 |
1650 |
1530 |
1250 |
130 |
CD−400PW |
465 |
1450 |
1780 |
1690 |
1450 |
130 |
CD−500PW |
580 |
1550 |
1895 |
1790 |
1650 |
130 |